Guide des spécifications des câbles ADSS : sélection de la portée, de la flèche et de la charge du vent

Guide des spécifications des câbles ADSS : sélection de la portée, de la flèche et de la charge du vent

ADSS (All-Dielectric Self-Supporting) cable is the standard choice for aerial fiber deployment on power line towers and utility poles — but only when correctly specified. Wrong span length selection, underestimated wind loading, or incorrect sag design leads to cable failure and outages. This guide gives telecom engineers the specification framework to get it right.

What Is ADSS Fiber Optic Cable?

ADSS cable is a fully dielectric (non-metallic) self-supporting aerial fiber cable designed for installation on power transmission towers and distribution poles.

  • All-dielectric: No metallic elements — safe on high-voltage lines, no grounding required
  • Autoportant : Aramid (Kevlar) strength members span between poles without a separate messenger wire
  • Classé pour l'extérieur : UV-resistant PE jacket (or AT jacket for high-voltage environments)
  • High fiber count: Available from 12F to 144F (288F+ on request)

Span Length Classification

ClasseRated SpanApplication typique
Service léger50-100 mUrban distribution, short spans
Service moyen100-200 mSuburban distribution lines
Série Heavy Duty200-400 mRural distribution, transmission
Ultra-lourd400-600 mLong-span transmission lines
Encadrement Sur Mesure600-1200 mRiver crossings, mountain terrain

Sag Calculation Fundamentals

ADSS cable forms a catenary curve between support points. The relationship between span, sag, and tension:

Sag (m) = (W × L²) / (8 × T)

Where: W = cable weight per meter (N/m), L = span length (m), T = horizontal tension (N)

Target Sag by Span

Longueur d'envergureTypical Sag (%)Clearance Priority
50-100 m1.5-2.5%Road crossing, building clearance
100-200 m2.0-3.0%Electrical safety clearance
200-400 m2.5-4.0%Ground clearance, ice loading
400-600 m3.0-5.0%Terrain clearance, wind galloping

Wind Load Design: IEC 60826

Reference wind pressure formula: q = ½ × ρ × V² × Cd

Where: ρ = 1.225 kg/m³ (air density at sea level), V = design wind speed (m/s), Cd = 1.0–1.2 for cylindrical cables

Wind Load Zones

AdrénalineDesign Wind SpeedReference PressureRégion typique
Vent faible≤ 25 m / s≤ 380 PaLow-wind inland
Medium Wind26 à 35 m/s380 à 750 PaMost of China, Europe interior
Vent fort36 à 45 m/s750 à 1240 PaCoastal, typhoon zones
Very High Wind46 à 60 m/s1240 à 2200 PaTyphoon/hurricane exposure

Chargement de glace

In ice-prone climates, combined ice+wind loading is the governing design case. Standard ice load assumptions:

  • Light ice zone: 5 mm radial ice, 700 kg/m³ density
  • Medium ice zone: 10–15 mm, combined with 50% wind
  • Heavy ice zone: 20–30 mm, combined with reduced wind

A 200m span designed for wind-only may fail under combined ice+wind if undersized. Always check the governing load combination.

Cable OD vs Span Relationship

Nombre de fibresDiamètre extérieur typique (mm)Poids (kg / km)Max Span at 25 m/s
12er étage–24e étage11 – 13 mm95–120 kg/km200-400 m
48er étage–72e étage13 – 16 mm120–160 kg/km150-300 m
96er étage–144e étage16 – 19 mm160–200 kg/km100-200 m

Larger cable diameter = more wind surface area = greater tension requirement. Specify minimum necessary fiber count to minimize OD and cost.

AT Jacket vs PE Jacket Selection

Type de vesteFaite une demandeSeuil de tension
PE (Standard)Distribution lines, low voltageJusqu'à 35kV
AT (Anti-pistage)Transmission lines, high voltage35–500 kV

Rule: if the cable attachment point is within 15m of a bare conductor at 110 kV+, specify AT jacket.

ADSS Procurement Specification Checklist

  1. Maximum span length (meters) — design span, not average
  2. Design wind speed (m/s) or reference wind pressure (Pa)
  3. Ice loading zone (if applicable)
  4. Required fiber count and fiber type (G.652D or G.657A1)
  5. Jacket type: PE or AT (based on line voltage)
  6. Minimum Rated Tensile Strength (RTS): typically 15–40 kN
  7. Plage de température d'installation
  8. Certifications: IEC 60794-1/60794-4, GB/T 17737.1, or Bellcore GR-20

AIMIFIBER ADSS Cable Range

  • Fiber count: 12F, 24F, 36F, 48F, 72F, 96F, 144F
  • Fiber type: G.652D (standard SMF) and G.657A1 (bend-insensitive)
  • Jacket: Standard PE or AT anti-tracking PE
  • Rated Tensile Strength: 8 kN, 12 kN, 20 kN, 30 kN, 40 kN
  • Certifications: IEC 60794-1-2, IEC 60794-4, GB/T 13993.3
  • MOQ: 1 drum (typically 2–4 km)
Need a Site-Specific ADSS Specification?
Send your span data, line voltage, and wind zone to AIMIFIBER for a custom cable specification with sag-tension calculations. Response within 24 hours.
Request ADSS Specification →
Installation d'un câble à fibre optique aérien ADSS sur un pylône électrique | AIMIFIBER
Photo de Sophie Wang

Sophie Wang

10 ans d'expérience dans les produits de télécommunication à fibre optique

Nouvelles récentes

Je m'abonne

Recevez les dernières informations sur les produits et les nouvelles de l'industrie.

Nous apprécions votre vie privée. Votre information restera confidentielle.

Contactez-Nous

Remplissez simplement votre nom, votre adresse e-mail et une brève description de votre demande dans ce formulaire. Nous vous contacterons dans les 24 heures.

AIMIT : votre fabricant de câbles à fibre optique de confiance

À propos d'aimit | AIMIFIBER

Avez-vous trouvé le câble dont vous avez besoin ou demandé un support personnalisé ?

Besoin d'un devis rapide ?

Des solutions de fibre optique fiables pour la connectivité

Laissez simplement votre message, nous vous contacterons dans les 2 heures ! 

Profil Aimifiber

Des solutions de fibre optique fiables pour la connectivité